Description
Key Benefits
- Hydrogen and Hydrocarbons flame detection.
- Ultra-fast detection mode detection within 5 milliseconds for fireballs or explosions
- High sensitivity – up to 100ft (30m) for a 1ft2 (0.1m2) n-heptane pan fire
- High immunity to false alarm
- Data/Event logger – alarms, faults and other relevant events are logged to non-volatile memory.
- Ethernet communication – in addition to the standard methods, such as 4-20mA and Modbus.
- Built-in-Test (BIT) – Automatic and manual internal self-test of window cleanliness and the overall operation of the detector (for both IR and UV channels).
- Window heater to avoid condensation and icing.
- Tilt mounting bracket can be connected either above or below the detector.
- Configurable detection mode – allows configuration of UV-IR, UV or IR detection mode.
Approvals
IP66 & 68 ; Nema 4X & 6P
Explosion Proof:
ATEX: II 2 G D
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C<Ta<75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C<Ta<85°C
IECEx
Ex db IIC T5 Gb -50°C≤Ta≤75°C
Ex db IIC T4 Gb -50°C≤Ta≤85°C
FM & FMC
Class I, Div. 1, Groups B, C & D; T4
Class I, Zone 1, AEx/Ex db IIC T4 Gb
T4 -50°C≤Ta≤85°C
T5 -50°C≤Ta≤75°C
Functional Safety
SIL2, per IEC 61508
Performance
ANSI FM 3260
EN54-10